EDT2412A

On-Off control

Selectable relay output for defrost or lighting

Single NTC probe input

Offset adjustment available for single NTC probe input

Compressor protection parameters can be set

Compressor operation, stop, or periodic operation can be adjusted in case of probe failure

Adjustable lower and upper limits for set values

Selectable smart defrost feature

Adjustable defrost time and interval

Six different options for audible alarm

Adjustable lower and upper alarm limits dependent on set value

Temperature can be displayed in °F or °C

External alarm, defrost, and lighting output can be activated via digital input

Ability to transfer parameters via ENDAKEY without powering the device

RS-485 ModBus RTU communication protocol

CE certified according to EN standards

Ambient/Storage Temperature 0 ... 50 °C / -25 ... 70 °C
Relative Humidity Works in environments with up to 80% humidity at 31 °C, decreasing linearly to 50% at 40 °C
Protection Class According to EN 60529 standard: Front panel: IP62, Rear panel: IP20
Altitude Up to 2000m
Supply Voltage 230V AC +10% -20% 50/60Hz or 10-30V DC / 8-24V AC
Power Consumption 5VA
Connection Screw terminal
Scale -60.0 ... 150.0 °C
Sensitivity 0.1 °C (Selectable as 0.1 °C or 1 °C)
Accuracy ±1 °C
Time Accuracy ±1%
Compressor Relay Output 8A model: 250V AC, 8A resistive load, NO+NC
1/2hp 240V AC inductive load
20A model: 277V AC, 20A resistive load, NO
2hp 277V AC inductive load
Defrost/Lighting Relay Output 8A model: 250V AC, 8A resistive load, NO+NC 1/2hp 240V AC inductive load
Compressor Relay Life 8A model: No load 30,000,000 operations; 250V AC, 8A resistive load 100,000 operations
20A model: No load 10,000,000 operations; 277V AC, 20A (for resistive load) 100,000 operations
Defrost/Lighting Relay Life EDT2412A-X-R: No load 30,000,000 operations; 250V AC, 8A resistive load 100,000 operations
Control Type Single set-value control and lighting control
Control Method On-Off control
Hysteresis Adjustable between 1...20.0 °C
Mounting Type Mounted by clamping to the panel
Dimensions 77x35x61 mm
Weight Approximately 190g (with packaging)
Enclosure Material Self-extinguishing plastics used

More Products in Cooling, Air Conditioning, and Defrost Control Devices