English
×
All rights reserved. All content and visuals used on our site
belong to Emos Group and unauthorized use is subject to legal action.
Inviva
ECOOL 1036 ECOOL 1036
ECOOL 1036

EMOS GROUP
Innovative Technologies with Strong Solutions,
Assurance in Quality!

ECOOL 1036

180x230x66 mm Sized, 3 NTC Inputs, DIN Input, 6 Relay Outputs Cold Room Control Device

PDF

Whatsapp

ECOOL 1036

180x230x66 mm sized

Control for fan-assisted cooling rooms

On-Off control

Six relay outputs for cooling, defrost, fan, lighting, alarm, and auxiliary (aux) control

Three NTC probe inputs for cooling, defrost, and optional indicator

Two digital inputs in total, adjustable for door control and parameters

Offset adjustment for NTC probe inputs

Compressor protection feature with parameters

Compressor operation, stop, or periodic operation in case of probe failure

Selectable smart defrost feature

Manual, fast defrost feature

Defrost based on time and evaporator temperature or manual defrost option

Adjustable lower and upper limits for set values

Adjustable defrost duration and interval

Lower and upper alarm limits dependent on the set value can be adjusted

Temperature unit can be displayed in °F or °C

RS485 Modbus RTU communication protocol

CE marked according to EN standards

Ambient/Storage Temperature 0...50 °C / -25...70 °C (without frost formation)
Relative Humidity Works in environments with up to 80% humidity at 31 °C, decreasing linearly to 50% at 40 °C
Protection Class According to EN 60529 standard: IP65
Altitude Up to 2000m
Supply Voltage 230V AC +10% -20%, 50/60Hz
Power Consumption Up to 5.6VA
Connection Socket terminal for 2.5 and 1.75 mm² wires
Scale -60.0...+150.0°C (-76.0 ... +302°F)
Sensitivity 0.1 °C (Selectable as 0.1 °C or 1 °C)
Accuracy ±1 °C
Time Accuracy ±1%
Indicator 120x70mm, top 3-digit single-point, bottom 4-digit double-point display (top with minus sign)
EMC EN 61326-1: 2013
Safety Requirements EN 61010-1: 2010 (Pollution degree 2, overvoltage category II)
Compressor Relay Output For resistive load: NO 277V AC 30A, for inductive load: 2hp 250V AC
Defrost Relay Output For resistive load: NO 250V AC 16A, for inductive load: 1/2hp 240V AC
Fan Relay Output For resistive load: NO 250V AC 16A, for inductive load: 1/2hp 240V AC
Lighting Relay Output For resistive load: NO 250V AC 16A, for inductive load: 1/2hp 240V AC
Alarm Relay Output For resistive load: NO 250V AC 8A, NC 250V 8A, for inductive load: 1/2hp 240V AC
Auxiliary (AUX) Relay Output For resistive load: NO 277V AC 30A, for inductive load: 2hp 250V AC
Relay Life Compressor Relay: Mechanical 10,000,000 operations (without load), Electrical 100,000 operations (20A 277V AC, resistive load)
Defrost Relay: Mechanical 30,000,000 operations (without load), Electrical 100,000 operations (16A 250V AC, resistive load)
Fan Relay: Mechanical 30,000,000 operations (without load), Electrical 100,000 operations (16A 250V AC, resistive load)
Lighting Relay: Mechanical 30,000,000 operations (without load), Electrical 100,000 operations (16A 250V AC, resistive load)
Alarm Relay: Mechanical 30,000,000 operations (without load), Electrical 100,000 operations (8A 250V AC, resistive load)
Auxiliary Relay: Mechanical 30,000,000 operations (without load), Electrical 100,000 operations (8A 250V AC, resistive load)
Control Type Compressor, defrost, fan, lighting, alarm, and auxiliary output control with set values and digital inputs
Control Method On-Off control
Hysteresis Adjustable between 1...20.0 °C
Mounting Type Wall mounting
Dimensions 180x230x66 mm
Weight Approximately 1150g (with packaging)
Enclosure Material Self-extinguishing plastics used

More Products in Cooling, Air Conditioning, and Defrost Control Devices