GLC-196T

GLC-196T PLC CPU Module: 24 VDC power supply, 9 inputs, 6 transistor outputs (450 mA), 3 channels with 20 kHz pulse, modular structure (16 expansions, 271 points), Ethernet, RS232/RS485, MODBUS RTU, 196 kB memory, DIN rail mount, 3 encoders/fast counters.

Whatsapp

GLC-196T

PLC CPU Module

24 VDC power supply

9 Channels 24 VDC PNP/NPN inputs

6 Channels transistor output (450mA @ 24VDC, PNP) CPU

3 Channels 20 kHz Pulse Output

Modular structure, supports up to 271 points with a maximum of 16 expansion modules

Access via network with 100MB ethernet port

RS232 and RS485 communication ports

MODBUS RTU Master/Slave protocol support

Decimal processing support

196 kB program / 10 kB variable memory

Maximum 20 kHz program cycle speed

DIN RAIL mount

Supports 3 differential (A, B, Z) encoder connections or 3 high-speed counter inputs (20 kHz)

Power Supply 24VDC (+/- 15% tolerance)
Power Consumption 3W max
Program Cycle Speed 20 kHz max
Programming Language Ladder Editor
Commands Logical, mathematical, communication, high-speed counters and pulse outputs, time and counting relays, special-purpose function blocks
Certification CE marked
Ethernet Port 100MB ethernet port, program loading, link establishment
Mini USB Port Program loading, link establishment
RS-232 Port Serial port, 4800..115200 baudrate range, supports ModBUS RTU protocol
RS-485 Port Serial port, 4800..115200 baudrate range, supports ModBUS RTU protocol
Digital Inputs 9 channels, 16.5 – 26VDC PNP/NPN, can connect 3 differential (A, B, Z) encoders or 3 high-speed counters (20 kHz)
Digital Outputs 6 channels 24VDC 450mA short-circuit protected PNP transistor output
Program Memory 196kB
Variable Memory 10kB
Temperature 0°C to +50°C (without freezing)
Humidity 5% rH to 95% rH (without condensation)